Switchgear

Outdoor switch

Auto Recloser
+
  • Auto Recloser

Auto Recloser

Keyword: Auto Recloser

Details

The FAR series Auto circuit recloser integrates the functions of control, protection,  measurement,communication,fault detection,on-line monitoring of closing or opening.comply to IEC62271 and ANSI/IEEE C37.60 standard.

General

Farady Electric strives to bring our customers the latest technology and competitive pricing and best service for pole mounted Auto circuit recloser.

The FAR series Auto circuit recloser can use on overhead distribution lines as well as distribution substation applications for all voltage classes 11kV up to 38kV at 50/60HZ power system. And its rated current can reach 1600A.

Service Condition

A. Air temperature: Maximum temperature: +85℃; Minimum temperature:-45℃.

B. Humidity: Monthly average humidity 95%; Daily average humidity 90% .

C. Altitude above sea level: Maximum installation altitude: 2500m or more higher.

D. Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.

E. No frequent violent shake.

Product Structure

FAR series 15KV 27KV 38KV AUTO Circuit Recloser01

1

ON/OFF Indicator

2

Emergency Close

3

Counter

4

Manual OFF

5

Earthing

6

Secondary Socket

7

Magnet Mechanism

 

 

 

 

Production's Characters Description
 
FAR series 15KV 27KV 38KV AUTO Circuit Recloser02
1. High quality Solid Epoxy resin material
2. Fully comply with ANSI std
3. Guarantee 30,000 times operation Environment friendly , Oil / SF6 Gas free
4. Suitable for both Pole mounted or Substation available
5. Reliable and Enhanced Life Expectancy
6. Ambient temp: -40℃~80℃
1Rogowski coil2Voltage Sensor3Vacuum Interrupter
4CT5Conductor6Push Rod
7Push Reed    
Production's Characters Description
1. High quality Vacuum Interrupter
2. Voltage sensor Integrated
3. CT Integrated
4. Reliable Push rod
5. Minimized moving components
6. Maintenance free design
FAR series 15KV 27KV 38KV AUTO Circuit Recloser03

Controller

1.1 Description

1.Voltlogic-351 series recloser controller is medium voltage overhead line grid monitoring unit, It can combined with vacuum circuit breaker for achieve of automatic reclose, measure monitoring, fault analysis and event records. It gives us a safety power grid for cutting line fault and automatic recovery operation and power automation.

2.The controller is suitable for up to 38kV outdoor switchgear using, include: vacuum circuit breakers, oil circuit breakers and gas circuit breakers.

3.The controller is gathering with line protection, control, measurement and monitoring of voltage and current signals integrated automation and control devices outdoors.

4.The controller is a automatic management unit for single way/multi ways/ring network/two power sourcing, provided with all voltage and current signals and all functions.

5.The controller column switch intelligent controller supports:

Wireless (GSM/GPRS/CDMA), Ethernet mode, WIFI, optical fiber, power line carrier, RS232/485, RJ45 and other forms of communication, and can access other station premises equipment (such as TTU, FTU, DTU, etc.).

FAR series 15KV 27KV 38KV AUTO Circuit Recloser04
1.2 Protection functions

Protection functions

ANSI code

Name in Device

Phase overcurrent

50P

P.OC

Overload

49

Overload

Phase Time-Overcurrent

51P

P.Curve

Ground Overcurrent

50G/N

E.F

Recloser

79

Reclose

Phase overcurrent cold load pick-up

CLPU 50

Cold Load

Switch-Onto-Fault

 

SOTF

Undervoltage

27

Under volt

Overvoltage

50P

P.OC

1.3 Metering
1.Phase current IA, IB, IC RMS, Zero Sequency
2.Voltage Uab,Ubc,Uca,U0 
3.Active power, reactive power and power factor
4.Frequency
1.4 Control and monitoring

Circuit breaker control

94

Latching /acknowledgement

86

1.5 Features
A.Protection configuration is complete, and all protection functions can be switched on and off fiexibly.
B.6 channels signal input.
C.4 channels current measure. 
D.4 channels voltage measure.
E.Large capacity flash memory can record at least 100 times of historical events, and no data will loss even the power is off.
F.Circuits operating loop can be used both the direct or alternating current, self-adaptation open/close brake function, which can co-work with various of breakers, and the operation is simple and reliable.
G.The device has complete self-inspection function to in-service monitor the working conditions of various parts of the device, ensuring the reliability of the device.
1.6 Records
A.Trip logs
B.SOE logs
C.Alarm Logs
1.7 Communication
1.RS485, RS232 port and Ethernet
2.Protocols -IEC60870-5-101, IEC60870-5-104 IEC61850 or Modbus RTU,DNP3.0
1.8 HMI Software
FAR series 15KV 27KV 38KV AUTO Circuit Recloser05

User Interface

The operator interface is designed to provide a r friendly method of controlling to user, viewing menus, entering settings and retrieving data from the relay. Four buttons are provided for navigation around the menu structure.

FAR series 15KV 27KV 38KV AUTO Circuit Recloser06

Projects

FAR series 15KV 27KV 38KV AUTO Circuit Recloser07

Installation

FAR series 15KV 27KV 38KV AUTO Circuit Recloser08

Related products

Leave a Message Online


If you are interested in our products, please leave your email address to receive a free product quote. Thank you!