Transformer

Dry Type Transformer
+
  • Dry Type Transformer

Dry Type Transformer

Category:

Keyword: Dry Type Transformer

Details

General   
Farady Electric manufacture a complete range of three phase distribution transformers, including oil-immersed type & cast resin dry-type transformer, we always designed with increased margins of safety and reliablity,and meet the following standard:   
IEC60076, IEEE Std, GB1094   
Application   
SC(B)10 series three phase resin-cast dry-type distribution transformer are in conformity with standard of IEC60076,with features of low loss, compact and light weight, low noise level,clamp-proof,anti-fouling,high mechanical strength, flame resisting, strong overload ability and low partial discharge quality,they are application to power transmission and distribution system,hotel,restaurant,commercial building,stadiums,chemical plants,stations,aiports,offshore drilling platforms,especially to heavy load centers and places with special fire protection requirements   
Mainly rating, types & capacity:   
Three phase,   
Two windings or three windings    
On-load or no-load voltage tapping changer    
Natural cooling or force air    
10-2500kVA   
Service condition   
a) Suitable for indoor or outdoor application   
b)Air temperature: 

  • Maximum temperature: +40℃; Minimum temperature:-30℃

c) Humidity: 

  • Monthly average humidity 95%; Daily average humidity 90% .

d) Altitude above sea level: 

  • Maximum installation altitude: 2000m.

e)Max wind speed:35M/s

f) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.

g) No frequent violent shake

Note: * Beyond those services condition should enquiry to manufacturer technical dept during order

High reliability feature: 

  • Flame resistant    
  • Explosion proof
  • Low temperature rise
  • Low loss & low noise
  • No environmental contamination

Technical Specification(11kv Series)

Type

Voltage combination

Vector group

Loss(W)

Impedance%

Dimension(L*W*H)mm

Weight(kg)

Primary(KV)

Tapping range

Secondary (KV)

No Load loss

Full load loss

SC(B)10-30/10



6  
6.3  
6.6  
10  
10.5  
11  
13.2  
13.8  
15

±2x2.5%

0.4 or  
other

Yyn0  
   or  
Dyn11

190 

700 

4.0 

680*400*686

300 

SC(B)10-50/10

270 

990 

690*400*686

360 

SC(B)10-80/10

360 

1370 

730*450*796

500 

SC(B)10-100/10

400 

1570 

730*500*816

600 

SC(B)10-125/10

470 

1840 

780*600*950

700 

SC(B)10-160/10

540 

2120 

950*650*1124

850 

SC(B)10-200/10

620 

2520 

990*650*1164

950 

SC(B)10-250/10

720 

2750 

1020*650*1207

1100 

SC(B)10-315/10

880 

3460 

1050*750*1320

1250 

SC(B)10-400/10

970 

3980 

1100*800*1450

1550 

SC(B)10-500/10

1160 

4880 

1140*800*1430

1850 

SC(B)10-630/10

1340 

5870 

1250*800*1500

1900 

SC(B)10-800/10

1520 

6950 

6.0 

1330*800*1540

2200 

SC(B)10-1000/10

1760 

8120 

1400*960*1640

2750 

SC(B)10-1250/10

2090 

9690 

1450*960*1690

3300 

SC(B)10-1600/10

2450 

11730 

1560*960*1930

4000 

SC(B)10-2000/10

3320 

14450 

1680*960*1930

4800 

SC(B)10-2500/10

3600 

17170 

1720*1010*1950

5500 

Note: *The above parameter is only subject to our standard design, special requirement can be customized

(20kv Series)

Type

Voltage combination

Vector group

Loss(W)

Impedance%

Dimension(L*W*H)mm

Weight(kg)

Primary(KV)

Tapping range

Secondary(KV)

No Load loss

Full load loss

SC(B)10-30/20

20

22

24

±2x2.5%

0.4 or other

Yyn0 or

Dyn11

220

800

6

980*480*750

435

SC(B)10-50/20

340

1240

1100*480*780

522

SC(B)10-80/20

410

1500

1160*500*800

725

SC(B)10-100/20

540

2000

1200*510*850

870

SC(B)10-125/20

580

2100

1200*600*900

1015

SC(B)10-160/20

680

2470

1220*650*1124

1233

SC(B)10-200/20

740

2950

1250*650*1164

1378

SC(B)10-250/20

800

3200

1280*670*1207

1595

SC(B)10-315/20

970

4090

1300*750*1400

1813

SC(B)10-400/20

1150

4850

1320*800*1450

2248

SC(B)10-500/20

1350

5800

1350*800*1490

2683

SC(B)10-630/20

1530

6840

1360*800*1530

2755

SC(B)10-800/20

1760

8270

1380*800*1580

3190

SC(B)10-1000/20

2070

9790

1430*960*1680

3988

SC(B)10-1250/20

2390

11540

1470*960*1720

4785

SC(B)10-1600/20

2790

13870

1560*960*1800

5800

SC(B)10-2000/20

3240

16390

1790*960*1930

6960

SC(B)10-2500/20

3870

19380

1800*1010*1950

7975

Note: *The above parameter is only subject to our standard design, special requirement can be customized

(35kv Series)

Type

Voltage combination

Vector group

Loss(W)

Impedance%

Dimension(L*W*H)mm

Weight
(kg)

Primar(KV)

Tapping range

Secondar(KV)

No Load loss

Full load loss

SC(B)10-30/35

33
34.5
35

±2x2.5
%

0.4 or
other

Yyn0
   or
Dyn11

300 

1350 

6.5 

1000*500*750

544 

SC(B)10-50/35

380 

1490 

1180*530*780

653 

SC(B)10-80/35

500 

1950 

1190*550*800

906 

SC(B)10-100/35

640 

2400 

1220*560*850

1088 

SC(B)10-125/35

750 

2640 

1240*600*900

1269 

SC(B)10-160/35

820 

3100 

1260*670*1124

1541 

SC(B)10-200/35

900 

3700 

1290*690*1164

1722 

SC(B)10-250/35

1080 

4350 

1320*700*1207

1994 

SC(B)10-315/35

1250 

4400 

1380*780*1400

2266 

SC(B)10-400/35

1550 

5660 

1400*830*1450

2809 

SC(B)10-500/35

1800 

6970 

1430*850*1490

3353 

SC(B)10-630/35

2070 

8120 

1460*890*1530

3444 

SC(B)10-800/35

2430 

9630 

1500*910*1580

3988 

SC(B)10-1000/35

2700 

11070 

1520*960*1680

4984 

SC(B)10-1250/35

3150 

13400 

1540*980*1720

5981 

SC(B)10-1600/35

3600 

16200 

1590*1000*1800

7250 

SC(B)10-2000/35

4230 

19100 

1830*1020*1930

8700 

SC(B)10-2500/35

4950 

22900 

1900*1090*1950

9969 

Note: *The above parameter is only subject to our standard design, special requirement can be customized