LW3F type pole-mounted SF6 load break switch was used in 12kV,24kV,33kV rated voltage, rated current 400/630A; 50/60HZ with the load current; over load current of power line open circuit and opening and closing electric systems.

General

The switch can equipped with a controller with most advanced technical parameter.

LW3F-A type LW3F is manually LBS for choice.

LW3F-M type LW3F is a intelligent type LBS for choice.

It can automatically disconnect when the distribution line was break down.

It could operated by handle; Implement electrification and distant. The electric controller was installed in stainless steel cabinet. So it could use in any conditions.

LW3F series 15KV 27KV 38KV SF6 Load Break Switch01

Service Condition

a) Air temperature:

Maximum temperature: +40 ; Minimum temperature:-20.

b) Humidity:

Monthly average humidity 95%; Daily average humidity 90%.

c) Altitude above sea level:

Maximum installation altitude: 2500m.

d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.

e) No frequent violent shake.

LW3F series 15KV 27KV 38KV SF6 Load Break Switch02

TECHNICAL DATA

No

Item

Unit

Data

1

Rated voltage

kV

12-20-33

2

Rated current

Hz

50/60

3

Rated insulation level (with SF6 gas 0.07Mpa)

lightning impulse voltage

kV

75/125/170

Power frequency impulse voltage

kV

42/50/70

5

Rated current

A

630

6

Rated open circuit load current (0.07Mpa//20℃  /h)

A

630

7

Open circuit current under 0 pressure

A

630

8

Rate peak value withstand current

kA

50

9

Rated short-time closing current

kA

50

10

Rated short-time withstand current

kA/s

1月20日

11

Rated electric cable charge open circuit current

A

25

12

Rated wire charge open circuit current

A

16

13

Rated closed loop open circuit current

A

630

14

Excitation current

A

21

15

Rated current open circuit times

400 times

16

Rated working pressure

MPa

0.07

17

Each operating voltage and resistance

 

150

18

Gas relative leakage rate

year

1%

19

SF6 gas moisture content

Leave factory relative figure

ppm

150

Switch working figure

ppm

300

20

Machine stable operation

times

6000

21

Rated operating voltage and assistant loop rated voltage

V

DC220;110

AC 220;110

22

Weight

M type

kg

115

A type

135

Product Structure

LW3F series 15KV 27KV 38KV SF6 Load Break Switch03

Product Characters:

  • High quality porcelain or Rubber bushing
  • Full comply with IEC std
  • Guarantee 4000 times operations
  • Environment friendly
  • Suitable for both Pole mounted or Hanging mounted
  • Reliable and Enhanced Life Expectancy
  • Ambient Temp:-40℃~+ 80℃

Operation Handle

ON/OFF Indication

Installation Bracket

Operating Mechanism

Interrupter

Hanging Lug

Cable Bushing

 

 

 

 

Controller

1.1 Description

LW3F series 15KV 27KV 38KV SF6 Load Break Switch04

Volt logic series line sectional load break controller is medium voltage overhead line grid monitoring unit, It can combined with load break switch for achieve of measure monitoring, fault analysis and event records. It gives us a safety power grid for cutting line fault and automatic recovery operation and power automation.

The controller is gathering with line protection, control, measurement and monitoring of voltage and current signals integrated automation and control devices outdoors.

The controller is a automatic management unit for single way/multi ways/ring network /two power sourcing, provided with all voltage and current signals and all functions.

The controller column switch intelligent controller supports:Wireless (GSM/GPRS/CDMA), Ethernet mode, WIFI, optical fiber, power line carrier, RS232/485, RJ45 and other forms of communication, and can access other station premises equipment (such as TTU, FTU, DTU, etc.).

1.2 Protection functions

Protection functions

ANSI code

Name in Device

Phase overcurrent

50P

P.OC

Overload

49

Overload

Phase Time-Overcurrent

51P

P.Curve

Ground Overcurrent

50G/N

E.F

Recloser

79

Reclose

Phase overcurrent cold load pick-up

CLPU50

Cold Load

Switch-Onto-Fault

 

SOTF

Undervoltage

27

Under volt

Overvoltage

50P

P.OC

1.3 Metering
  • Phase current IA, IB, IC RMS, Zero Sequency
  • Voltage Uab, Ubc, Uca, U0
  • Active power, reactive power and power factor
  • Frequency
1.4 Control and monitoring

Switch control

94

Lockout Relay

86

1.5 Features
  • Protection configuration is complete, and all protection functions can be switched on and off flexibly.
  • 13 channels digital signal input.
  • 4 channels current measure.
  • 6 channels voltage measure.
  • Large capacity flash memory can record at least 100 times of historical events and no data will loss even the power is off.
1.6 Records
  • Trip logs
  • SOE logs
  • Alarm Logs
1.7 Communication
  • RS485, RS232 port and Ethernet
  • Protocols -IEC60870-5-101, IEC60870-5-104
  • IEC61850 or Modbus RTU,DNP3.0
1.8 HMI Software
LW3F series 15KV 27KV 38KV SF6 Load Break Switch05

Dimensions

LW3F series 15KV 27KV 38KV SF6 Load Break Switch06
15KV SF6 LOAD BREAK SWITCH
LW3F series 15KV 27KV 38KV SF6 Load Break Switch07
24KV SF6 LOAD BREAK SWITCH
LW3F series 15KV 27KV 38KV SF6 Load Break Switch08
36KV SF6 LOAD BREAK SWITCH
Installation
LW3F series 15KV 27KV 38KV SF6 Load Break Switch09

Related products

Leave a Message Online


If you are interested in our products, please leave your email address to receive a free product quote. Thank you!